Appearance
Points
A point is one data channel on a device, usually one Modbus register. Its configuration sets how to read the register, how to scale the value, and which alert thresholds apply. Point endpoints also send commands to switch, motor, display, and alarm points.
Point routes use the numeric device id as {device_id}; serial numbers are not accepted here. {id} is the numeric point ID.
The point object
json
{
"id": 12,
"agri_id": "d-1000-abcd-1-00",
"device_id": 5,
"name": "Inlet Temperature",
"slave_id": 1,
"address": 0,
"the_type": 1,
"the_type_detail": {
"the_type": 1,
"name": "Temperature",
"name_en": "Temperature",
"name_zh_hans": "温度",
"unit": "℃",
"value_type": 1,
"icon_url": "https://dl.yengear.com/media/icon/temp.png",
"is_shared": true
},
"data_endian": ">",
"data_endian_display": "Big-Endian (ABCD)",
"data_type": "int16",
"data_type_display": "16-bit Integer",
"data_index": 0,
"modbus_type": 3,
"modbus_type_display": "Holding Register",
"data_scale": 0.1,
"data_delta": 0.0,
"min_value": null,
"max_value": null,
"info": null,
"enabled": true
}| Field | Type | Default | Description |
|---|---|---|---|
id | integer | — | Point ID (read-only) |
agri_id | string | — | {device_agri_id}-{slave_id}-{address}{data_index} (read-only) |
device_id | integer | — | Parent device ID (read-only) |
name | string | null | null | Point name, up to 32 characters |
slave_id | integer | 0 | Modbus slave ID |
address | integer | 0 | Register address, 0–65535 |
data_index | integer | 0 | Offset for multi-register reads, 0–9 |
the_type | integer | 0 | Point type ID; see List configuration options |
the_type_detail | object | — | Point type name, unit, value type, and icon (read-only) |
modbus_type | integer | 3 | 0 unknown, 1 coil, 2 discrete input, 3 holding register, 4 input register |
data_type | string | int16 | int8, uint16, int16, uint32, int32, float32, or f32_2_i16 |
data_endian | string | > | @ auto, > ABCD, < DCBA, <_SB BADC, <_SW CDAB |
data_scale | number | 1 | Value = raw × data_scale + data_delta |
data_delta | number | 0 | Offset added after scaling |
min_value | number | null | null | Lower alert threshold |
max_value | number | null | null | Upper alert threshold |
enabled | boolean | true | Whether the device reads the point |
info | string | null | null | Note, up to 64 characters |
modbus_type_display, data_type_display, and data_endian_display carry the labels for the coded fields.
Device models with capability bit 0x20 allow full point configuration. On other models, only name and info can change, and create, delete, duplicate, and threshold requests return 400.
List points
http
GET /api/v2/projects/{project_id}/devices/{device_id}/points/Returns the device's points ordered by slave_id, address, and data_index.
Authentication
Bearer token. Minimum role: Read-only.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
Example request
bash
curl 'https://dl.yengear.com/api/v2/projects/proj_AbCdEfGhIj/devices/5/points/' \
-H 'Authorization: Bearer YOUR_API_TOKEN'Responses
200: Array of point objects, not paginated. Cached until a point changes.403: The project is outside the token's scope.404: The device is not in the organization.
Retrieve a point
http
GET /api/v2/projects/{project_id}/devices/{device_id}/points/{id}/Returns one point.
Authentication
Bearer token. Minimum role: Read-only.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
id | integer | Yes | Point ID |
Responses
200: The point object.404: The point or device does not exist in the organization.
Create a point
http
POST /api/v2/projects/{project_id}/devices/{device_id}/points/Adds a point to a device.
Authentication
Bearer token. Minimum role: Manager.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
Request body
Any writable field of the point object. Omitted fields take their defaults. Send slave_id, address, and data_index explicitly: together they identify the point and form its agri_id.
Example request
bash
curl -X POST 'https://dl.yengear.com/api/v2/projects/proj_AbCdEfGhIj/devices/5/points/' \
-H 'Authorization: Bearer YOUR_API_TOKEN' \
-H 'Content-Type: application/json' \
-d '{
"name": "Inlet Temperature",
"slave_id": 1,
"address": 0,
"data_index": 0,
"the_type": 1,
"modbus_type": 3,
"data_type": "int16",
"data_endian": ">",
"data_scale": 0.1
}'Responses
201: The created point object.400: A point with the sameslave_id,address, anddata_indexexists; the device model does not allow editing points; or a threshold is invalid.403: Role below Manager, or the plan's point quota is reached (membership_quota_exceeded).
Update a point
http
PATCH /api/v2/projects/{project_id}/devices/{device_id}/points/{id}/Updates point fields. PUT behaves the same as PATCH: send only the fields to change.
Authentication
Bearer token. Minimum role: Manager.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
id | integer | Yes | Point ID |
Example request
bash
curl -X PATCH 'https://dl.yengear.com/api/v2/projects/proj_AbCdEfGhIj/devices/5/points/12/' \
-H 'Authorization: Bearer YOUR_API_TOKEN' \
-H 'Content-Type: application/json' \
-d '{"data_scale": 0.01, "info": "Scaled to volts"}'Responses
200: The updated point object.400: Validation error, or a field other thannameandinfoon a device model that does not allow editing points.
Delete a point
http
DELETE /api/v2/projects/{project_id}/devices/{device_id}/points/{id}/Deletes a point.
Authentication
Bearer token. Minimum role: Manager.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
id | integer | Yes | Point ID |
Responses
204: Point deleted.400: The device model does not allow editing points.409point_in_use: Automations or other configuration still reference the point. Remove the references first.
Duplicate a point
http
POST /api/v2/projects/{project_id}/devices/{device_id}/points/{id}/duplicate/Copies a point. The copy gets the next free data_index for the same slave_id and address, and its name gains the suffix _<data_index + 1>.
Authentication
Bearer token. Minimum role: Manager.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
id | integer | Yes | Point ID to copy |
Responses
201: The new point object.400: The device model does not allow editing points.
Send a switch or motor command
http
POST /api/v2/projects/{project_id}/devices/{device_id}/points/{id}/{command}/Sends a command to a switch or motor point through the platform gateway. A 200 response means the gateway accepted the command; check the point value or the operation log for the field result.
Authentication
Bearer token. Minimum role: Operator. When the plan is read-only, off and stop stay available for safety shutdowns.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
id | integer | Yes | Point ID |
command | string | Yes | on, off, forward (motor forward), antiport (motor reverse), or stop |
Request body
| Name | Type | Required | Description |
|---|---|---|---|
r_token | string | No | Your request token, 1–32 characters without surrounding spaces. Also accepted as the r_token query parameter; if you send both, they must match. The server generates a 12-character token when omitted. |
Example request
bash
curl -X POST 'https://dl.yengear.com/api/v2/projects/proj_AbCdEfGhIj/devices/5/points/18/on/' \
-H 'Authorization: Bearer YOUR_API_TOKEN' \
-H 'Content-Type: application/json' \
-d '{"r_token": "pump-on-0001"}'Example response
json
{
"success": true,
"data": {
"success": true,
"data": {},
"message": "Operation succeeded",
"token": "pump-on-0001"
},
"error": null
}data.message is display text from the gateway. data.token is the request token. Store it to match the command with device acknowledgements and the project's point operation log.
Responses
200: The gateway accepted the command.400: Invalidr_token, or the gateway rejected the command (error.messageholds the reason).403: Role below Operator, or the plan is read-only and the command is notofforstop.
Set display content
http
POST /api/v2/projects/{project_id}/devices/{device_id}/points/{id}/set-content/Sends text to an LED or digit display point.
Authentication
Bearer token. Minimum role: Operator.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
id | integer | Yes | Point ID |
Request body
| Name | Type | Required | Description |
|---|---|---|---|
content | string | Yes | Text to display |
r_token | string | No | Request token, as in Send a switch or motor command |
Example request
bash
curl -X POST 'https://dl.yengear.com/api/v2/projects/proj_AbCdEfGhIj/devices/5/points/21/set-content/' \
-H 'Authorization: Bearer YOUR_API_TOKEN' \
-H 'Content-Type: application/json' \
-d '{"content": "Gate 3 open"}'Responses
200: Same body as Send a switch or motor command.400:contentis missing or not a string, or the gateway rejected the command.
Set an alarm level
http
POST /api/v2/projects/{project_id}/devices/{device_id}/points/{id}/set-alarm-level/Sets the level of an alarm point.
Authentication
Bearer token. Minimum role: Operator.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
id | integer | Yes | Point ID |
Request body
| Name | Type | Required | Description |
|---|---|---|---|
level | integer | Yes | Alarm level, 0–5 |
r_token | string | No | Request token |
Responses
200: Same body as Send a switch or motor command.400:levelis missing or outside 0–5, or the gateway rejected the command.
Retrieve the latest point value
http
GET /api/v2/projects/{project_id}/devices/{device_id}/points/{id}/current-data/Returns the point's latest value from the real-time store.
Authentication
Bearer token. Minimum role: Read-only.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
id | integer | Yes | Point ID |
Example response
json
{
"success": true,
"data": {
"agri_id": "d-1000-abcd-1-00",
"value": 24.5,
"the_type": 1,
"unit": "℃",
"t": 1704758400,
"project_id": "proj_AbCdEfGhIj",
"org_slug": "yengear"
},
"error": null
}Responses
200: A data item. For a point that has never reported,datacontains onlyagri_id.503: The real-time store is unavailable.
Set thresholds
http
POST /api/v2/projects/{project_id}/devices/{device_id}/points/{id}/set-threshold/Sets the alert range of a sensor point.
Authentication
Bearer token. Minimum role: Manager.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
id | integer | Yes | Point ID |
Request body
| Name | Type | Required | Description |
|---|---|---|---|
min_value | number | null | No | Lower threshold; null clears it |
max_value | number | null | No | Upper threshold; null clears it |
Only sensor-type points accept thresholds. Values must be finite. When both thresholds are set, min_value must be lower than max_value, counting the stored value of a field you leave out.
Example request
bash
curl -X POST 'https://dl.yengear.com/api/v2/projects/proj_AbCdEfGhIj/devices/5/points/12/set-threshold/' \
-H 'Authorization: Bearer YOUR_API_TOKEN' \
-H 'Content-Type: application/json' \
-d '{"min_value": 5.0, "max_value": 35.0}'Responses
200:datacontainsmin_valueandmax_value.400: The point is not a sensor type, a value is invalid,min_valueis not lower thanmax_value, or the device model does not allow editing points.
List points with thresholds
http
GET /api/v2/projects/{project_id}/devices/{device_id}/points/threshold-points/Returns the device's points that have min_value or max_value set.
Authentication
Bearer token. Minimum role: Read-only.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
Responses
200: Array of point objects.
List configuration options
http
GET /api/v2/projects/{project_id}/devices/{device_id}/points/options/Returns the values accepted by modbus_type, data_type, data_endian, and the_type. Each *_choices entry is a [value, label] pair; send the value. point_types lists shared types first, then the organization's custom types.
Authentication
Bearer token. Minimum role: Read-only.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
project_id | string | Yes | Project identifier |
device_id | integer | Yes | Device ID |
Example response
json
{
"success": true,
"data": {
"modbus_type_choices": [[0, "Unknown"], [1, "Coil"], [2, "Discrete Input"], [3, "Holding Register"], [4, "Input Register"]],
"data_type_choices": [["int8", "8-bit Integer"], ["uint16", "16-bit Unsigned Integer"], ["int16", "16-bit Integer"], ["uint32", "32-bit Unsigned Integer"], ["int32", "32-bit Integer"], ["float32", "32-bit Float"], ["f32_2_i16", "32-bit Float from 2x16-bit"]],
"data_endian_choices": [["@", "Auto"], [">", "Big-Endian (ABCD)"], ["<", "Little-Endian (DCBA)"], ["<_SB", "Little-Endian (BADC)"], ["<_SW", "Little-Endian (CDAB)"]],
"point_types": [
{ "the_type": 1, "name": "Temperature", "name_en": "Temperature", "name_zh_hans": "温度", "unit": "℃", "value_type": 1, "icon_url": "https://dl.yengear.com/media/icon/temp.png", "is_shared": true }
]
},
"error": null
}Responses
200: Configuration options.
List point history
http
GET /api/v2/data/{point_agri_id}/Returns saved readings of one point, newest first. The API checks that the point's device belongs to the caller's organization and project scope.
Authentication
Bearer token. Minimum role: Read-only.
Path parameters
| Name | Type | Required | Description |
|---|---|---|---|
point_agri_id | string | Yes | Point agri_id, for example d-1000-abcd-1-00 |
Query parameters
| Name | Type | Required | Description |
|---|---|---|---|
page | integer | No | Page number. Default 1. |
page_size | integer | No | Records per page. Default 50. Keep it to a few hundred at most. |
min_timestamp | integer | No | Earliest t to return, in Unix seconds. Default: 90 days ago. |
Example request
bash
curl 'https://dl.yengear.com/api/v2/data/d-1000-abcd-1-00/?page=1&page_size=50&min_timestamp=1704758400' \
-H 'Authorization: Bearer YOUR_API_TOKEN'Example response
json
{
"success": true,
"data": {
"count": 100,
"next": "?page=2&page_size=50",
"previous": null,
"results": [
{ "agri_id": "d-1000-abcd-1-00", "v": 24.2, "t": 1704758400 }
]
},
"error": null
}History records name the value v, while live endpoints use value. next and previous are query strings to append to the same path.
Responses
200: A page of readings.400:pageorpage_sizeis not an integer.404: The device does not exist or is outside the caller's scope.