Skip to content

Y412-22/44/88-L Wireless I/O Module Specification ​

Y412-22-L (2-channel)Y412-44-L (4-channel)Y412-88-L (8-channel)
Y412-22-LY412-44-LY412-88-L

Contents ​

  1. Overview
  2. Ordering Information
  3. Key Features
  4. Technical Specifications
  5. Interfaces and Indicators
  6. Mechanical and Environmental
  7. Installation and Wiring
  8. Important Notes

1. Overview ​

The Y412 series is a LoRa-based Wireless I/O Module family for dry-contact input acquisition and relay output control. It carries input states between master/slave nodes and remote relay outputs.

  • Y412-22-L: 2DI / 2DO
  • Y412-44-L: 4DI / 4DO
  • Y412-88-L: 8DI / 8DO

The series supports master/slave mode, bidirectional follow or unidirectional feedback, and momentary or latching control.

Y412 dimensions

2. Ordering Information ​

Model Naming ​

text
Y412-XX-L
  |   |  `-- L: LoRa wireless communication
  |   `----- XX: channel count (22 / 44 / 88)
  `--------- Y412: wireless I/O module series

Model Matrix ​

ModelDI ChannelsDO ChannelsDescription
Y412-22-L22Dual-channel Wireless I/O Module
Y412-44-L44Four-channel Wireless I/O Module
Y412-88-L88Eight-channel Wireless I/O Module

3. Key Features ​

  • DIP-selectable master/slave role, control direction, and output action
  • Local push-buttons for channel testing and local operation
  • Dry-contact/NPN inputs and Form A relay outputs
  • DIN rail mounting for control-cabinet installation

4. Technical Specifications ​

Wireless ​

ParameterSpecification
Operating frequency410.125 to 493.125 MHz (ISM)
Transmit power30 dBm (max. approx. 1W)
Receiver sensitivity-148 dBm @ 2.4 Kbps
Max. range5 km standard; 10 km option available for selected configurations
Channels32 (set by DIP switches 1 to 5)
Air data modeRange priority (default) / balanced / response priority
Antenna connectorSMA

Electrical ​

ParameterSpecification
Supply (DC version)8 to 28V DC
Supply (AC version)85 to 265V AC
Average current70 mA @ 12V DC
TX current290 mA @ 12V DC
Current per energized relay15 mA @ 12V DC
DI input typeDry contact / NPN
DO output typeForm A relay (NO + COM)
Relay contact rating5A 30V DC / 5A 250V AC

5. Interfaces and Indicators ​

Port Description ​

  • DI: digital input terminals (2 / 4 / 8 channels, depending on model)
  • COM: common terminal for DI
  • DO COM: relay common terminal
  • DO NO: relay normally open terminal
  • RS485 A/B/G: configuration and commissioning interface
  • Power terminals:
    • DC version: V+ / V- / PE
    • AC version: L / N / PE

LED Indicators ​

LEDColorDescription
OUT1 to OUT8RedRelay output status for each channel
POWERGreenPower status
TXD / RXDGreenWireless transmit / receive activity
RSSI1 to RSSI3GreenSignal strength level
MODEBlueMode or encryption status

Y412 front panel

6. Mechanical and Environmental ​

Mechanical Specifications ​

ParameterY412-22-LY412-44-LY412-88-L
Dimensions108 x 87.5 x 65 mm108 x 87.5 x 65 mm108 x 87.5 x 65 mm
Weight (DC)184 g +/- 5 g196 g +/- 5 g226 g +/- 5 g
Weight (AC)194 g +/- 5 g206 g +/- 5 g236 g +/- 5 g
Operating temperature-40 to +85 degC-40 to +85 degC-40 to +85 degC
Operating humidity5% to 95% RH, non-condensing5% to 95% RH, non-condensing5% to 95% RH, non-condensing
Storage temperature-60 to +125 degC-60 to +125 degC-60 to +125 degC
Storage humidity5% to 95% RH, non-condensing5% to 95% RH, non-condensing5% to 95% RH, non-condensing
Mounting35 mm DIN rail35 mm DIN rail35 mm DIN rail

7. Installation and Wiring ​

Use the user manual for AC/DC power, DI, and relay wiring, DIP switch settings, and commissioning.

AC and DC supplies are separate hardware versions. Match the supply to the unit label. DI accepts dry contacts or NPN open-collector outputs; it is not a voltage input. Relay contacts require an external load supply.

8. Important Notes ​

  • Use one master per communication group, matching channel settings, and compatible operating modes.
  • Radio range depends on antenna placement, obstructions, interference, and air-data mode. Response-priority mode trades range for faster response.
  • Timeout reset and advanced parameters are configurable through a compatible RS485/serial tool. Check the supplied settings before relying on communication-loss behavior.
  • Local keys and wireless control do not replace an independent emergency-stop or personnel-safety circuit.

  • Manufacturer: Hunan YenGear Tech Co., Ltd.
  • Address: Room 21014, Building 1, Fudi Xingguang Tiandi, Yingxin Road, Yuhua District, Changsha, Hunan, China
  • Email: hi@yengear.com
  • Website: www.yengear.com