Skip to content

Y406-22/44/66/88/GG-L LoRa Wireless Controller Specification ​

Y406-44-L controller with Y406T-44-L handheld remote

Contents ​

  1. Overview
  2. Ordering Information
  3. Key Features
  4. Technical Specifications
  5. Interfaces and Indicators
  6. Dimensions and Mounting
  7. Installation and Wiring
  8. Important Notes

1. Overview ​

Y406 is a LoRa wireless controller series for handheld operation of relay-controlled equipment. It offers 2, 4, 6, 8, or 16 control circuits for applications such as pumps, fans, lighting, and valves. RS485 functions depend on the supplied hardware and firmware; compatible PLC expansion-board firmware reports remote key states over Modbus RTU.

2. Ordering Information ​

2.1 Model Selection ​

ModelControl circuitsDI / DO model code
Y406-22-L22 / 2
Y406-44-L44 / 4
Y406-66-L66 / 6
Y406-88-L88 / 8
Y406-GG-L1616 / 16

In Y406-XX-L, the two code positions represent DI / DO counts; each G means 16, and L means LoRa. Use the supplied terminal diagram for physical input and output connections.

2.2 Power Supply and Remote Selection ​

Controller supply: 9–72 V DC. Specify the controller model when ordering.

Order the remote model, key layout, antenna, and accessories with the controller. Custom key labels identify the operator's actions; use the key configuration supplied with the controller.

3. Key Features ​

  • Handheld LoRa operation for relay-controlled equipment.
  • Local relay contacts for load switching.
  • Modbus RTU key-state reads over RS485 with compatible PLC expansion-board firmware.
  • Handheld remote setup through Remote Configurator requires a compatible BLE configuration module and firmware.

4. Technical Specifications ​

4.1 Wireless ​

ParameterSpecification
Wireless technologyLoRa
Operating frequency433 MHz reference radio version; use the frequency specified for the ordered unit
AntennaExternal antenna
Remote rangeUp to 3 km without obstruction; actual range depends on site conditions

4.2 Electrical and I/O ​

ParameterSpecification
Controller power supply9–72 V DC
Control circuits2 / 4 / 6 / 8 / 16, depending on model
Local relay outputsRelay contacts rated at 10 A / 250 V AC

For PLC communication parameters, register mapping, and complete Modbus RTU read examples, see the User Manual.

5. Interfaces and Indicators ​

Interface / indicatorDescription
Power9–72 V DC input; follow the unit's wiring diagram and polarity markings
Relay contacts10 A / 250 V AC; follow the unit's wiring diagram
RS485Use the supplied model's terminal drawing for A/B connections
AntennaExternal antenna connection
Remote TX / RX indicatorsTransmit/receive indicators on Y406T-44-L

A remote acknowledgement means the module received the command. Verify relay and equipment operation directly.

6. Dimensions and Mounting ​

6.1 Dimensions ​

Dimensions use width × height × depth.

ModelController dimensions (W × H × D)
Y406-22-L95 × 110 × 45 mm
Y406-44-L95 × 110 × 45 mm
Y406-66-L95 × 110 × 45 mm
Y406-88-L125 × 110 × 45 mm
Y406-GG-L180 × 100 × 50 mm

6.2 Mounting ​

Allow access to the antenna connector and terminals. Use the production drawing for mounting holes and installation clearances.

7. Installation and Wiring ​

See the User Manual for antenna placement, power wiring, and relay connections.

8. Important Notes ​

  • Do not use Y406 for safety-rated emergency stops or control that requires guaranteed timing.
  • Check communication-loss and power-recovery behavior before operating equipment.
  • Use the protocol supplied for the controller model and firmware for RS485 commands.
  • Y406 does not include 4G, Wi-Fi, Ethernet, cloud services, or LoRaWAN gateway connectivity.